Swimming Pool Dehumidifier Sizing

Overview

Swimming Pool Dehumidifier Sizing and Load Determination Overview

This application note highlights the source of moisture loads in pool room enclosures and its potential harmful effects if left uncontrolled.

View or Download Printable Version

Sources Of Moisture Load

 

Indoor pools have three main sources of moisture:

  1. Evaporation from pool water surfaces
  2. Outdoor ventilation air
  3. People

The vapor pressure difference between pool water and the air causes continuous evaporation. The vapor pressure of both water and air will change based upon each one’s temperature and the differences in their temperatures. The evaporation rate increases the higher the water temperature is in relationship to the air temperature. The activity level at the water surface will also either increase or decrease the evaporation rate. Activity factors as defined by the ASHRAE Applications Handbook are shown in Table 2 of this bulletin.

During the summer months, outdoor ventilation air that is being introduced into the space to meet local code requirements may also be contributing to the moisture load of the space depending on the climate location.

The presence of spectators also adds to the moisture load of the space. This load is typically minimal in residential pools but can be fairly substantial when bleacher spectator areas are present. 

Problems With Humidity

 

Air is a gas. Like most gases, it expands in volume when heated and contracts in volume when cooled. This expansion or contraction that occurs with changing temperatures increases or decreases the percentage of moisture that the air can hold. In other words, as air expands, its ability to hold moisture increases. For a given moisture content, the percentage of moisture to air volume (relative humidity) is reduced when air is heated.

Condensation

 

Condensation is one of the major enemies to an indoor pool environment. When condensation develops on surfaces, it can damage the material it forms on and also provides food for fungi and bacteria to grow.

Visible condensation will appear when the surface temperature is below the indoor dew point of the space. (See Figure 1.) In most pool environments, this dew point is in the range of 58° F to 66° F. The surface temperature can be calculated using the formula:

Ts = Ti – (K x (1/R) x (Ti – To))

Ts = Surface Temperature

Ti = Indoor Temperature

K = Constant of 0.68 for Vertical Surface

R = R Value of Structural Panel

To = Outdoor Temperature

Since windows are the major contributor to condensation in this environment, we will only look at this building component. However, the same process can be used for any building component. Windows typically do not have an R value but are rated with U values. The U value is the reciprocal of the R value, R = 1/U.

The U values published for windows are for the entire window assembly and do not reflect the U value for each component of the window. For this reason we recommend that you add 5° F to the actual calculated surface temperature and use this value for your dew point. This would mean that all surfaces in an indoor pool environment should be kept above 63° F to 71° F to prevent visible condensation.

If you’re more comfortable referencing percent relative humidity, Graph’s 1, 2 and 3 show what percent relative humidity that surface condensation will appear for different U values at indoor space temperatures of 76° F, 82° F and 86° F with outdoor temperatures of 25° F, 0° F, and -25° F.

Graph 1 - % RH for Various U Values at 25 degrees Farenheit Graph 2 - % RH for Various U Values at 0 degrees Farenheit OA Graph 3 - % RH for Various U Values at -25 degrees Farenheit
Graph 1 - % RH for Various U Values at 25° F OA Graph 2 - % RH for Various U Values at 0° F OA Graph 3 - % RH for Various U Values at -25° F OA

 

Humidity Range

 

The American Society of Heating Refrigeration and Air Conditioning Engineers (ASHRAE) recommends that you maintain between 50% and 60% relative humidity in an indoor pool environment. Relative humidity above 60% will be uncomfortable to the occupants of the space, promotes the growth of certain fungi and bacteria and makes it more difficult to prevent visible condensation. A relative humidity below 50% will cause evaporative cooling on swimmers’ skin as they exit the water, giving them a chilling effect. Lower humidity levels will also cause more water evaporation, requiring more make-up water and more chemical usage, therefore requiring larger equipment and an increase in operating costs. Figure 1 - Proper Dew Point of Pool Room Surfaces
Figure 1 - Proper Dew Point of Pool Room Surfaces

 

Methods Of Humidity Control

 

Several different techniques can be used to reduce humidity in an indoor pool environment. One of the oldest and most common practices in years past was to use a make-up air / exhaust method. Warm moist air is exhausted to the outdoors and new outdoor air is introduced into the building. (See Figure 2.) During the winter months, this air needs to be heated to the room temperature before entering the space. A high operating cost is associated with this process. During the spring, summer and fall in certain parts of the country, the outdoor air actually may have more moisture in it than the indoor environment. This will cause the indoor humidity to rise and potentially cause building damage.

Make-Up Air / Exhaust Method
Figure 2 - Make-Up Air / Exhaust Method

 

In some parts of the country, the outdoor air may be drier than the indoor environment. At first glance, it appears that this solves all humidity problems. As long as the indoor humidity is below 60% RH, there shouldn’t be a problem. However, considering today’s high energy costs, we also must add operating costs into the equation. If we take a 75 foot by 25 foot pool that has an average depth of 6 feet, we find that this contains 84,000 gallons of water. Let’s assume that the space is maintained using outdoor air and we are in a dry climate, say constantly below 30% relative humidity.

This pool is evaporating 85.3 pounds of moisture per hour or 10.3 gallons per hour. This means in 340 days the pool is empty. If we maintain 50% relative humidity in the space, the evaporation rate decreases to 52 lbs/hr or 6.24 gallons per hour. In the same 340 days, we have saved the cost of over 50,000 gallons of make-up water. Also associated with this savings is the energy to reheat this water and the chemical costs to treat it. We have reduced the makeup water and chemical costs by about 40%.

The most effective method of maintaining appropriate relative humidity levels and achieving these types of savings is to use a refrigerationbased dehumidification system. (See Figure 3.)

 Refrigeration-Based Dehumidification System
Figure 3 - Refrigeration-Based Dehumidification System

 

Calculation Of Moisture Load

Table 1 provides ASHRAE’s recommended design temperatures for indoor pools. The table indicates a maximum of 90° F air temperature (Elderly Swimmers). While not shown in the table, ASHRAE also suggests that the air temperature should not exceed 86° F which would be above the comfort threshold. Also, most refrigeration circuits are only designed for a maximum of 90° F.

Table 1 - ASHRAE Recommended Air and Water Design Temperatures
Type of Facility Air Temperature Water Temperature
Recreational 75° F to 85° F 75° F to 85° F
Therapeutic 80° F to 85° F 85° F to 95° F
Competition 78° F to 85° F 76° F to 82° F
Diving 80° F to 85° F 80° F to 90° F
Elderly Swimmers 84° F to 90° F 85° F to 90° F
Hotel 82° F to 85° F 92° F to 86° F
Whirlpool / Spa 80° F to 85° F 97° F to 104° F

 

Discussion of the evaporation formula is beyond the scope of this application note. Desert Aire uses the latest information from the ASHRAE Applications Handbook. ASHRAE’s formula uses the vapor differential method of determining the evaporation rate from the water surface. This formula is used to develop the factors listed in Table 1. The values listed in Table 3 are based on 25 FPM of air movement across the surface of the water. Variations of this formula are available to account for an increase in air movement over the water surface.

All values in Table 3 are based on an activity factor of one (1) and are for the occupied times of operation. Table 2 lists different activity factors that can be applied to your end results based on the type of pool you are designing.

Please note that all unoccupied hours of operation should apply the activity factor of 0.5 to determine the evaporation rate.

Table 2 - Activities Factor Table from ASHRAE Applications Handbook 2007
Type of Pool Activity Factor
Baseline (Unoccupied Pool) 0.5
Residential Pool 0.5
Condominium 0.65
Therapy 0.65
Hotel 0.8
Public, School, YMCA 1.0
Whirlpool, Spas 1.0 to 1.5
Wavepools, Water Slides 1.5 or more

Table 3 - Evaporation Rates of Still Water at Sea Level

Ventilation Air

The amount of ventilation air required is generally accepted to be the amount as recommended by ASHRAE Standard 62.1. Most codes are based on this method but always check with your local code authority for the proper method of calculating this amount. The 2007 version of this standard recommends that this be based on the square footage of water surface at a rate of 0.48 cfm per square foot, while the square footage of the deck / floor area be calculated at some other rate, generally at 0.06 cfm per square foot. If the space includes a spectator area, which means a place where people can sit and watch, than you must also include 7.5 cfm per person plus 0.06 cfm per square foot of bleacher area.

This standard also suggests that when calculating the moisture of the ventilation air being introduced into the space that you use the ASHRAE Dehumidification Weather Data. Desert Aire recommends using the 1% weather conditions. A selection of cities and values across the United States and Canada are listed in Table 5.

The following formula is used to determine the amount of moisture in the ventilation air:

Moisture in lbs/hr = cfm x Δgrains / 1,555

Δgrains = value from Table 5 – value from Table 4

Table 4 - Moisture Content Guidelines (All Values Are at Sea Level)
Indoor Air Moisture Content
Inside Temperature 50% RH 60% RH
74° F 62 75
76° F 68 81
78° F 72 86
80° F 77 92
82° F 82 96
84° F 88 106
86° F 93 113
88° F 100 120

 

Table 5 - Geographic Outdoor Design Criteria (ASHRAE Fundamentals 1%)

 

Human Impact On Moisture

 

Moisture contributed by people is normally only accounted for when spectator or bleacher areas are part of the space design. Most design manuals will list the latent moisture per person in the values of btu/h. The values these manuals list are usually for indoor conditions below 80° F. Most indoor pools are above 80° F so 20% more latent must be added to the listed values in most design books. Desert Aire recommends a value of 190 btu/h per person. If you had 100 people, this would give you 19,000 btu/h of moisture. To convert this value to lbs/hr of moisture, use a factor of 1,061 btu/h per lb. Therefore, 19,000 btu/h is equal to 17.9 lbs/hr or about the same as the evaporation from a 400 square foot pool surface that is running at 82° F within the space, 80° F water and 55% RH.

Conclusion

 

Commercial pool enclosures must consider all three humidity load calculations – air, water and people – to determine the total moisture load. A design professional must still perform a sensible heating and cooling load to ensure that the selected equipment can maintain the space temperature during the entire year. This application note is only intended to give you a general understanding of what is involved in the calculation process. Please contact your nearest Desert Aire Representative for assistance with the design of your pool facility and dehumidification system.

Learn more:

How 3 Key Dehumidification Terms Relate

Ventilation Air For Indoor Pools

Interaction of Pool Water and Air Chemistry 

Swimming Pool Load Calculations

Related Products

ExpertAire™ Horizontal (LC) & Vertical (LV) Series Dehumidifier

ExpertAire™ Series commercial dehumidification systems provide you with highest Moisture Removal Efficiency ratings available -- and the flexibility to regulate the introduction of outdoor air, saving energy.

 

SelectAire™ (SA) and SelectAire Plus™ (SP) Series Dehumidifier

SelectAire™ and SelectAire Plus™ Series dehumidification systems respond to your toughest large capacity moisture challenges with modular engineering and flexible design options for customized, targeted solutions.